SINAMICS G120 PM240 Power Module, FSC
G120 模塊式設(shè)計(jì)變頻器功率模塊 PM250
3AC 380-480V 標(biāo)準(zhǔn)型 帶內(nèi)置A級(jí)濾波器
額定功率
kW (LO);15
額定輸出
電流 I (LO);32
額定功率
kW (HO);11
額定輸出
電流 I (HO);26
外形尺寸
FS;FSC
SIEMENS上海朔川電氣設(shè)備有限公司
聯(lián)系人 : 莫海群 聯(lián)系手機(jī):17321435985
聯(lián)系電話:021-60494465 在線商務(wù):1919057176
公司傳真:021-67263002請(qǐng)備注莫海群 收 謝謝
郵 箱:1919057176@qq.com
6SL3225-0BE31-1AA1
![]()
SINAMICS G120 POWER MODULE PM250 WITH BUILT IN CL. A FILTER POSSIBILITY OF REGENERATION 3AC380-480V +10/-10% 47-63HZ OUTPUT HIGH OVERLOAD: 11KW FOR 200% 3S,150% 57S,100% 240S AMBIENT TEMP -10 TO +50 DEG C OUTPUT LIGHT OVERLOAD: 15KW FOR 150% 3S,110% 57S,100% 240S AMBIENT TEMP -10 TO +40 DEG C 334 X 189 X 185 (HXWXD), FSC PROTECTION IP20 WITHOUT CONTROL UNIT AND BO
|
The SINAMICS G120 frequency inverter is designed to provide precise and cost-effective speed/torque control of three-phase motors.
With different device versions (frame sizes FSA to FSGX) in a power range from 0.37 kW to 250 kW (0.5 hp to 400 hp), it is suitable for a wide variety of drive solutions.
Example: SINAMICS G120, frame sizes FSA, FSB and FSC; each with Power Module, CU240E‑2 F Control Unit and Basic Operator Panel BOP-2
Example: SINAMICS G120, frame sizes FSD, FSE and FSF; each with Power Module, CU240E‑2 F Control Unit and Inbligent Operator Panel IOP
Example: SINAMICS G120, frame size FSGX; with Power Module, CU240E‑2 F Control Unit and Basic Operator Panel BOP-2
SINAMICS G120 is a modular inverter system that essentially comprises two function units:
The Control Unit controls and monitors the Power Module and the connected motor using several different closed-loop control types that can be selected. It supports communication with a local or central controller and monitoring devices.
The Power Module supplies the motor in the power range 0.37 kW to 250 kW (0.5 hp to 400 hp). It features state-of-the-art IGBT technology with pulse-b-modulated motor voltage and selectable pulse frequency. Comprehensive protection functions provide a high degree of protection for the Power Module and the motor.
The Control Units can be combined with the following Power Modules:
Control Units |
Power Modules degree of protection IP20 |
|||
---|---|---|---|---|
|
PM230 1) |
PM240‑2 |
PM240 |
PM250 |
CU230P‑2 |
✓ |
✓ |
✓ |
✓ |
CU240B‑2 |
✓ |
✓ |
✓ |
✓ |
CU240E‑2 |
✓ |
✓ |
✓ |
✓ |
CU250S‑2 |
– |
✓ |
✓ |
✓ |
1) PM230 Power Modules with integrated filter class A or class B, degree of protection IP55/UL Type 12, 0.37 kW to 90 kW (0.5 to 125 hp) are integral components of the SINAMICS G120P for pumps, fans and compressors. The CU230P‑2 is the Control Unit for SINAMICS G120P and SINAMICS G120P Cabinet for pumps, fans and compressors.More inbation can be found in Catalog D 35.
SINAMICS G120 standard inverters are available in different versions for safety-related applications. The PM240‑2 und PM250 Power Modules are already designed for Safety Integrated. PM240 Power Modules, frame size FSGX (i.e. 160 kW/250 hp and higher) are approved only for the Basic Safety functions (STO, SS1, and SBC). A drive can be combined with a Control Unit with safety functions (see overview) in order to create a Safety Integrated drive. The availability of Safety Integrated functions depends on the type of Control Unit.
Control Unit |
Basic Safety functions |
Extended Safety functions |
||||
---|---|---|---|---|---|---|
|
STO |
SS1 |
SBC 1) |
SLS |
SDI |
SSM |
CU230P‑2 |
– |
– |
– |
– |
– |
– |
CU240B‑2 |
– |
– |
– |
– |
– |
– |
CU240E‑2 |
✓ |
– |
– |
– |
– |
– |
CU240E‑2 F |
✓ |
✓ |
– |
✓ |
✓ |
✓ 2) |
CU250S‑2 |
✓ |
✓ |
✓ |
✓ 3) |
✓ 3) |
✓ 3) |
1) The SBC function can be utilized only if a Safe Brake Relay is installed.
2) SSM possible only for CU240E‑2 DP‑F / CU240E‑2 PN‑F Control Units with PROFIsafe.
3) With license for Extended Safety functions.
Basic Safety functions (certified according to IEC 61508 SIL 2, and EN ISO 13849‑1 PL d and Category 3)
Extended Safety functions (certified according to IEC 61508 SIL 2 and EN ISO 13849‑1 PL d and Category 3)
Basic Safety and Extended Safety functions can be activated via PROFIsafe or by means of the safety bs.
None of the safety functions require a motor encoder and they are thus cheaper and easier to implement. Existing systems in particular can be simply updated with safety technology without the need to change the motor or mechanical system.
The Safe Torque Off (STO) function can be used without restriction for all applications. The SS1, SLS, SSM and SDI functions are only permissible for applications where the load can never accelerate when the inverter is switched off. They are therefore not permitted for applications involving pull-through loads such as hoisting gear and unwinders.
Additional inbation is provided in chapter Highlights, section Safety Integrated.
The innovative Efficient Infeed Technology is employed in PM250 Power Modules. This technology allows the energy produced by motors operating in generator mode connected to standard inverters to be fed back into the supply system. For control cabinets, an additional temperature rise can be avoided and the amount of space required can be reduced due to the fact that components such as braking resistors, braking choppers and line reactors can be eliminated. Further, wiring and engineering costs are significantly reduced. At the same time, energy consumption can be reduced and ongoing operating costs noticeably reduced.
Additional inbation is provided in chapter Highlights, section Efficient Infeed Technology.
The new cooling system and varnishing of the electronic modules significantly increases the service life or useful life of the device.
Integrated technologies help when optimizing the energy usage of the plant or system referred to the particular application:
Additional inbation is provided in chapter Highlights, section Energy efficiency.
SINAMICS G120 standard inverters are modular inverters for standard drives. Selection of the SINAMICS G120 is reduced to two or three steps thanks to the modular system used.
The optimum Control Unit is selected first, based on the number of I/Os and any additional functions required such as Safety Integrated or HVAC. The communication options are already integrated and do not have to be additionally ordered or plugged in. Three product series are available corresponding to the particular application.
CU230P‑2 Control Units
The CU230P‑2 Control Units have been specifically designed for pump, fan and compressor applications.
The CU230P‑2 is the Control Unit for the pump, fan and compressor inverters SINAMICS G120P and SINAMICS G120P Cabinet. More inbation can be found in Catalog D 35.
CU240B‑2 and CU240E‑2 Control Units
The CU240B‑2 and CU240E‑2 Control Units are suitable for a wide range of applications in general machine construction, such as conveyor belts, mixers and extruders.
CU250S‑2 Control Units
The CU250S‑2 Control Units are suitable for applications involving single drives with exacting speed control requirements such as extruders and centrifuges, and for bing tasks such as conveyor belts, lifting/lowering devices, etc. They can also be used to implement multi-motor drives without DC coupling such as wire-drawing machines and simple material lines.
Debion |
Fieldbus |
Profile |
Inputs |
Integrated safety technology |
Fail-safe |
Control Unit |
---|---|---|---|---|---|---|
|
|
|
|
|
|
Article No. |
CU230P‑2 series - the specialist for pumps, fans, compressors, water, buildings Technology functions (selection): Free function locks (FFB), 4 × PID controller, cascade connection, hibernation mode, essential service mode, multi-zone control |
||||||
CU230P‑2 HVAC |
|
– |
6 DI
3 DO |
– |
– |
6SL3243-0BB30-1HA3 |
CU230P‑2 DP |
|
|
6SL3243-0BB30-1PA3 |
|||
CU230P‑2 PN |
|
|
6SL3243-0BB30-1FA0 |
|||
|
– |
|||||
CU240B‑2 series – for basic applications with variable-speed drives – without encoder Technology functions (selection): Free function blocks (FFB), 1 × PID controller, motor holding brake |
||||||
CU240B‑2 |
|
– |
4 DI
1 DO |
– |
– |
6SL3244-0BB00-1BA1 |
CU240B‑2 DP |
|
|
6SL3244-0BB00-1PA1 |
|||
CU240E‑2 series – for standard applications in general machinery construction, such as conveyor belts, mixers and extruders – without encoder Technology functions (selection): Free function blocks (FFB), 1 × PID controller, motor holding brake |
||||||
CU240E‑2 |
|
– |
6 DI
3 DO |
STO |
1 F-DI |
6SL3244-0BB12-1BA1 |
CU240E‑2 DP |
|
|
6SL3244-0BB12-1PA1 |
|||
CU240E‑2 PN |
|
|
6SL3244-0BB12-1FA0 |
|||
|
– |
|||||
CU240E‑2 F |
|
– |
STO, SS1, SLS, SDI |
3 F-DI |
6SL3244-0BB13-1BA1 |
|
CU240E‑2 DP‑F |
|
|
STO, SS1, SLS, SSM 1), SDI |
6SL3244-0BB13-1PA1 |
||
CU240E‑2 PN‑F |
|
|
6SL3244-0BB13-1FA0 |
|||
|
– |
|||||
CU250S‑2 series – for complex applications such as extruders and centrifuges – with and without encoder (basic ber (EPos) optional) Technology functions (selection): Free function blocks (FFB), 1 × PID controller, motor holding brake |
||||||
CU250S‑2 |
|
– |
11 DI
3 DO 4 DI/DO (DI can be used as high-speed bs) |
STO, SBC, SS1 |
3 F-DI
1 F-DO |
6SL3246-0BA22-1BA0 |
CU250S‑2 DP |
|
|
6SL3246-0BA22-1PA0 |
|||
CU250S‑2 PN |
|
|
6SL3246-0BA22-1FA0 |
|||
|
– |
|||||
CU250S‑2 CAN |
|
– |
6SL3246-0BA22-1CA0 |
1) SSM is possible only with PROFIsafe.
Debion |
Suitable for |
Article No. |
---|---|---|
SINAMICS SD card 512 MB + firmware V4.7 SP6 HF1 (Multicard V4.7 SP6 HF1) |
CU230P‑2 |
6SL3054-7TD00-2BA0 |
Debion |
SINAMICS SD card |
SINAMICS SD card |
Licenses (without SD card) |
---|---|---|---|
|
Article No. |
Article No. |
Article No. |
License Extended Functions |
6SL3054-4AG00-2AA0-Z E01 |
6SL3054-7TD00-2BA0-Z E01 |
6SL3074-7AA04-0AA0 |
License Extended Functions |
6SL3054-4AG00-2AA0-Z F01 |
6SL3054-7TD00-2BA0-Z F01 |
6SL3074-0AA10-0AA0 |
Licenses Extended Functions |
6SL3054-4AG00-2AA0-Z E01+F01 |
6SL3054-7TD00-2BA0-Z E01+F01 |
– |
Additional inbation on firmware V4.7 SP6 HF1:
https://support.industry.siemens.com/cs/document/109482094
Debion |
Suitable for |
Article No. |
---|---|---|
SINAMICS SD card 512 MB + firmware V4.6 (Multicard V4.6) |
CU230P‑2 |
6SL3054-7EG00-2BA0 |
SINAMICS SD card 512 MB + firmware V4.7 (Multicard V4.7) |
CU230P‑2 |
6SL3054-7EH00-2BA0 |
For more inbation on firmware V4.6:
https://support.industry.siemens.com/cs/document/67385235
For more inbation on firmware V4.7:
https://support.industry.siemens.com/cs/document/92554110
The optimum power unit can be quickly selected based on the required motor power, the supply voltage and the braking cycles to be expected. Power Modules in degree of protection IP20 are intended for installation in a control cabinet.
PM230 Power Modules – degree of protection IP20
PM230 Power Modules are designed for applications involving pumps, fans and compressors with a square characteristic. They do not have an integrated braking chopper (single-quadrant applications).
PM230 Power Modules with integrated filter class A or class B, degree of protection IP55/UL Type 12, 0.37 kW to 90 kW (0.5 to 125 hp) are integral components of the SINAMICS G120P for pumps, fans and compressors. More inbation can be found in Catalog D 35.
PM240‑2 and PM240 Power Modules – IP20 degree of protection
PM240‑2 Power Modules have an integrated braking chopper (four-quadrant applications) and are suitable for a large number of applications in general machinery construction. The same applies for PM240 Power Modules, but the PM240 Power Modules in frame size FSGX do not have an integrated braking chopper. A plug-in Braking Module is optionally available for this purpose.
PM250 Power Modules – degree of protection IP20
PM250 Power Modules are suitable for the same applications as the PM240‑2/PM240. Any braking energy is directly fed back into the line supply (four-quadrant applications – a braking resistor is not required).
The Power Modules can be combined with the following Control Units:
Control Units |
Power Modules degree of protection IP20 |
||
---|---|---|---|
|
PM230 1) |
PM240‑2/PM240 |
PM250 |
CU230P‑2 |
✓ |
✓ |
✓ |
CU240B‑2 |
✓ |
✓ |
✓ |
CU240E‑2 |
✓ |
✓ |
✓ |
CU250S‑2 |
– |
✓ |
✓ |
1) PM230 Power Modules with integrated filter class A or class B, degree of protection IP55/UL Type 12, 0.37 kW to 90 kW (0.5 to 125 hp) are integral components of the SINAMICS G120P for pumps, fans and compressors. The CU230P‑2 is the Control Unit for SINAMICS G120P and SINAMICS G120P Cabinet for pumps, fans and compressors.More inbation can be found in Catalog D 35.
PM230, PM240 and PM240‑2 Power Modules
Rated power 1) |
|
Rated output currentIrated2) |
PM230 Power Module The following Control Units are supported: CU230P‑2 ..., CU240B‑2 ..., CU240E‑2 ... |
|
PM240‑2 Power Modules 4) All CUs pluggable |
---|---|---|---|---|---|
kW |
hp |
A |
Article No. |
|
Article No. |
200 ... 240 V 1 AC/3 AC |
|||||
0.55 |
0.75 |
3.2 |
– |
|
6SL3210-1PB13-0❒L0 |
0.75 |
1 |
4.2 |
– |
|
6SL321❒-1PB13-8❒L0 |
1.1 |
1.5 |
6 |
– |
|
6SL3210-1PB15-5❒L0 |
1.5 |
2 |
7.4 |
– |
|
6SL3210-1PB17-4❒L0 |
2.2 |
3 |
10.4 |
– |
|
6SL321❒-1PB21-0❒L0 |
3 |
4 |
13.6 |
– |
|
6SL3210-1PB21-4❒L0 |
4 |
5 |
17.5 |
– |
|
6SL321❒-1PB21-8❒L0 |
200 ... 240 V 3 AC |
|||||
5.5 |
7.5 |
22 |
– |
|
6SL3210-1PC22-2❒L0 |
7.5 |
10 |
28 |
– |
|
6SL3210-1PC22-8❒L0 |
11 |
15 |
42 |
– |
NEW |
6SL3210-1PC24-2UL0 |
15 |
20 |
54 |
– |
NEW |
6SL3210-1PC25-4UL0 |
18.5 |
25 |
68 |
– |
NEW |
6SL3210-1PC26-8UL0 |
22 |
30 |
80 |
– |
NEW |
6SL3210-1PC28-0UL0 |
30 |
40 |
104 |
– |
NEW |
6SL3210-1PC31-1UL0 |
37 |
50 |
130 |
– |
NEW |
6SL3210-1PC31-3UL0 |
45 |
60 |
154 |
– |
NEW |
6SL3210-1PC31-6UL0 |
55 |
75 |
178 |
– |
NEW |
6SL3210-1PC31-8UL0 |
380 ... 480 V 3 AC |
|||||
0.37 5) |
0.5 |
1.3 |
6SL3210-1NE11-3❒L1 |
|
– 5) |
0.55 |
0.75 |
1.7 |
6SL3210-1NE11-7❒L1 |
|
6SL3210-1PE11-8❒L1 |
0.75 |
1 |
2.2 |
6SL3210-1NE12-2❒L1 |
|
6SL3210-1PE12-3❒L1 |
1.1 |
1.5 |
3.1 |
6SL3210-1NE13-1❒L1 |
|
6SL3210-1PE13-2❒L1 |
1.5 |
2 |
4.1 |
6SL3210-1NE14-1❒L1 |
|
6SL3210-1PE14-3❒L1 |
2.2 |
3 |
5.9 |
6SL3210-1NE15-8❒L1 |
|
6SL3210-1PE16-1❒L1 |
3 |
4 |
7.7 |
6SL321❒-1NE17-7❒L1 |
|
6SL321❒-1PE18-0❒L1 |
4 |
5 |
10.2 |
6SL3210-1NE21-0❒L1 |
|
6SL3210-1PE21-1❒L0 |
5.5 |
7.5 |
13.2 |
6SL3210-1NE21-3❒L1 |
|
6SL3210-1PE21-4❒L0 |
7.5 |
10 |
18 |
6SL321❒-1NE21-8❒L1 |
|
6SL321❒-1PE21-8❒L0 |
11 |
15 |
26 |
6SL3210-1NE22-6❒L1 |
|
6SL3210-1PE22-7❒L0 |
15 |
20 |
32 |
6SL3210-1NE23-2❒L1 |
|
6SL321❒-1PE23-3❒L0 |
18.5 |
25 |
38 |
6SL321❒-1NE23-8❒L1 |
NEW |
6SL3210-1PE23-8❒L0 |
22 |
30 |
45 |
6SL3210-1NE24-5❒L0 |
NEW |
6SL3210-1PE24-5❒L0 |
30 |
40 |
60 |
6SL3210-1NE26-0❒L0 |
NEW |
6SL3210-1PE26-0❒L0 |
37 |
50 |
75 |
6SL3210-1NE27-5❒L0 |
NEW |
6SL3210-1PE27-5❒L0 |
45 |
60 |
90 |
6SL3210-1NE28-8❒L0 |
NEW |
6SL3210-1PE28-8❒L0 |
55 |
75 |
110 |
6SL3210-1NE31-1❒L0 |
NEW |
6SL3210-1PE31-1❒L0 |
75 |
100 |
145 |
6SL3210-1NE31-5❒L0 |
NEW |
6SL3210-1PE31-5❒L0 |
90 |
125 |
178 |
– |
NEW |
6SL3210-1PE31-8❒L0 |
110 |
150 |
205 |
– |
NEW |
6SL3210-1PE32-1❒L0 |
132 |
200 |
250 |
– |
NEW |
6SL3210-1PE32-5❒L0 |
160 |
250 |
302 |
– |
4) |
6SL3224-0XE41-3UA0 |
200 |
300 |
370 |
– |
4) |
6SL3224-0XE41-6UA0 |
250 |
400 |
477 |
– |
4) |
6SL3224-0XE42-0UA0 |
500 ... 690 V 3 AC |
|||||
11 |
10 |
14 |
– |
NEW |
6SL3210-1PH21-4❒L0 |
15 |
15 |
19 |
– |
NEW |
6SL3210-1PH22-0❒L0 |
18.5 |
20 |
23 |
– |
NEW |
6SL3210-1PH22-3❒L0 |
22 |
25 |
27 |
– |
NEW |
6SL3210-1PH22-7❒L0 |
30 |
30 |
35 |
– |
NEW |
6SL3210-1PH23-5❒L0 |
37 |
40 |
42 |
– |
NEW |
6SL3210-1PH24-2❒L0 |
45 |
50 |
52 |
– |
NEW |
6SL3210-1PH25-2❒L0 |
55 |
60 |
62 |
– |
NEW |
6SL3210-1PH26-2❒L0 |
75 |
75 |
80 |
– |
NEW |
6SL3210-1PH28-0❒L0 |
90 |
100 |
100 |
– |
NEW |
6SL3210-1PH31-0❒L0 |
110 |
100 |
115 |
– |
NEW |
6SL3210-1PH31-2❒L0 |
132 |
125 |
142 |
– |
NEW |
6SL3210-1PH31-4❒L0 |
Heat sink variant |
|
|
↑ |
|
↑ |
Standard |
|
|
0 |
|
0 |
Push-through |
|
|
1 |
|
1 |
Integrated line filter |
|
|
↑ |
|
↑ |
Without |
(for IT systems) |
|
U |
|
U |
Class A |
(for TN systems) |
|
A |
|
A |
1) Rated power based on the rated output current Irated. The rated output current Irated is based on the duty cycle for low overload (LO). Low overload (LO) generally applies for applications with low dynamic response (continuous operation), quadratic torque characteristic with low break loose torque and low speed accuracy. Examples: Centrifugal pumps, radial/axial fans, rotary piston fans, radial compressors, vacuum pumps, chain conveyors, agitators. High Overload (HO) generally applies for applications with increased dynamic response (cyclic operation) and constant torque characteristics with high break loose torque. Examples: Gear pumps, eccentric worm pumps, mills, mixers, crushers, lifting/lowering gear, centrifuges.
2) The rated output current Irated is based on the duty cycle for low overload (LO). These current values are applicable for 200 V, 400 V or 690 V.
3) PM230 Power Modules with integrated filter class A or class B, degree of protection IP55/UL Type 12, 0.37 kW to 90 kW (0.5 to 125 hp) are integral components of the SINAMICS G120P for pumps, fans and compressors. The CU230P‑2 is the Control Unit for SINAMICS G120P and SINAMICS G120P Cabinet for pumps, fans and compressors.More inbation can be found in Catalog D 35.
4) 160 kW ... 250 kW (250 to 400 hp), PM240 Power Modules (frame size FSGX).
5) The PM240‑2 Power Module with Article No. 6SL3210-1PE11-8. L1 corresponds to 0.37 kW (0.5 hp) with duty cycle HO.
Data based on a duty cycle with low overload (LO). Data based on duty cycle with high overload (HO), see section Power Modules.
PM250 Power Modules
Rated power 1) |
|
Rated output currentIrated2) |
PM250 Power Module All CUs pluggable |
---|---|---|---|
kW |
hp |
A |
Article No. |
380 ... 480 V 3 AC |
|||
7.5 |
10 |
18 |
6SL3225-0BE25-5AA1 |
11 |
15 |
25 |
6SL3225-0BE27-5AA1 |
15 |
20 |
32 |
6SL3225-0BE31-1AA1 |
18.5 |
25 |
38 |
6SL3225-0BE31-5❒A0 |
22 |
30 |
45 |
6SL3225-0BE31-8❒A0 |
30 |
40 |
60 |
6SL3225-0BE32-2❒A0 |
37 |
50 |
75 |
6SL3225-0BE33-0❒A0 |
45 |
60 |
90 |
6SL3225-0BE33-7❒A0 |
55 |
75 |
110 |
6SL3225-0BE34-5❒A0 |
75 |
100 |
145 |
6SL3225-0BE35-5❒A0 |
90 |
125 |
178 |
6SL3225-0BE37-5❒A0 |
Integrated line filter |
|
|
↑ |
Without |
(for IT systems) |
|
U |
Class A |
(for TN systems) |
|
A |
Class B |
(for TN systems) |
|
Integrated line filter not available, as external option only |
1) Rated power based on the rated output current Irated. The rated output current Irated is based on the duty cycle for low overload (LO). Low overload (LO) generally applies for applications with low dynamic response (continuous operation), quadratic torque characteristic with low break loose torque and low speed accuracy. Examples: Centrifugal pumps, radial/axial fans, rotary piston fans, radial compressors, vacuum pumps, chain conveyors, agitators. High Overload (HO) generally applies for applications with increased dynamic response (cyclic operation) and constant torque characteristics with high break loose torque. Examples: Gear pumps, eccentric worm pumps, mills, mixers, crushers, lifting/lowering gear, centrifuges.
2) The rated output current Irated is based on the duty cycle for low overload (LO). These current values are applicable for 400 V.
Data based on a duty cycle with low overload (LO). Data based on duty cycle with high overload (HO), see section Power Modules.
Inbligent Operator Panel IOP
Graphic display with bar-type diagrams, e.g. for status values such as pressure or flowrate.
User-friendly commissioning, diagnostics and local operator control using a large plain text display, b menu navigation and application wizards.
Inbligent Operator Panel IOP Handheld
A handheld version of the IOP can be ordered for mobile use. In addition to the IOP, this includes a housing with rechargeable batteries, charging unit and RS232 connecting cable.
Basic Operator Panel BOP-2
Menu navigation and 2-line display permit fast and user-friendly commissioning of the inverter.
Simple basic commissioning by simultaneously displaying beter and beter value, as well as the option of filtering beters.
Door mounting kit for IOP/BOP‑2
Using the optionally available door mounting kit, the IOP/BOP‑2 can be mounted in a control cabinet door with just a few manual operations (IP54/UL Type 12 degree of protection is achieved).
Push-through mounting frame for push-through variants of the PM230 and PM240-2 Power Modules
It is advisable to use an optionally available mounting frame to install the push-through unit in a control cabinet. This mounting frame includes the necessary seals and frame to ensure compliance with degree of protection IP54. If the Power Module is installed without use of the optional mounting frame, the user is responsible for ensuring that the requisite degree of protection is provided. The kit contains all the necessary nuts and seals.
Memory card
The beter settings for an inverter can be stored on the SINAMICS SD card. When service is required, e.g. after the inverter has been replaced, the drive system is immediaby ready for use again. The memory card can also be used to upgrade the firmware of the Control Unit.
Brake Relay
The Brake Relay allows the Power Module to be connected to an electromechanical motor brake, thereby allowing the motor brake to be driven directly by the Control Unit.
Safe Brake Relay
The Safe Brake Relay allows the Power Module to be safely connected to an electromechanical motor brake, allowing the brake to be directly and safely controlled from the CU250S‑2 Control Unit in accordance with IEC 61508 SIL 2 and EN ISO 13849‑1 PL d and Category 3.
PC inverter connection kit 2
For controlling and commissioning an inverter directly from a PC if the appropriate software (STARTER commissioning tool or SINAMICS Startdrive) has been installed.
Shield connection kit for Power Modules
The shield connection kit makes it easier to connect the shields of supply and control cables, provides mechanical strain relief and thus ensures optimum EMC perbance. The shield connection kit is included in the scope of supply of the PM230 Power Modules, frame sizes FSA to FSC, and the PM240‑2 Power Modules, frame sizes FSA to FSF.
Shield connection kit for Control Units
The shield connection kit offers optimum shield connection and strain relief for all signal and communication cables. It includes a matching shield bonding plate and all of the necessary connecting and retaining elements for mounting.
Debion |
|
Article No. |
---|---|---|
Inbligent Operator Panel IOP |
|
|
|
|
6SL3255-0AA00-4JA1 |
|
NEW |
6SL3255-0AA00-4JC1 |
Operator Panel IOP Handheld |
|
6SL3255-0AA00-4HA0 |
Operator Panel BOP‑2 |
|
6SL3255-0AA00-4CA1 |
Door mounting kit for IOP/BOP‑2 |
|
6SL3256-0AP00-0JA0 |
Push-through mounting frame |
|
|
|
|
|
|
|
6SL3260-6AA00-0DA0 |
|
|
6SL3260-6AB00-0DA0 |
|
|
6SL3260-6AC00-0DA0 |
Memory card |
|
|
|
|
6SL3054-4AG00-2AA0 |
Brake Relay |
|
6SL3252-0BB00-0AA0 |
Safe Brake Relay |
|
6SL3252-0BB01-0AA0 |
PC inverter connection kit 2 |
|
6SL3255-0AA00-2CA0 |
Shield plates |
|
|
|
|
|
|
|
Supplied with the Power Modules, available as a spare part |
Shield connection kits |
|
|
|
|
|
|
|
6SL3262-1AD00-0DA0 |
|
|
6SL3262-1AF00-0DA0 |
|
|
|
|
|
Supplied with the Power Modules, available as a spare part |
|
|
|
|
|
6SL3262-1AC00-0DA0 |
|
|
6SL3262-1AD00-0DA0 |
|
|
6SL3262-1AF00-0DA0 |
|
|
|
|
|
6SL3264-1EA00-0FA0 |
|
|
6SL3264-1EA00-0HA0 |
|
|
6SL3264-1EA00-0HB0 |
|
|
6SL3264-1EA00-0LA0 |
STARTER commissioning tool 2) on DVD‑ROM |
|
6SL3072-0AA00-0AG0 |
SINAMICS Startdrive commissioning tool 3) on DVD‑ROM |
|
6SL3072-4DA02-0XG0 |
1) Approved only for CU230P‑2 HVAC and CU230P‑2 DP Control Units with firmware version V4.6 and higher.
2) The STARTER commissioning tool is also available on the Internet at http://www.siemens.com/starter
3) The SINAMICS Startdrive commissioning tool is also available on Internet athttps://support.industry.siemens.com/cs/document/68034568
The following line-side power components are available for SINAMICS G120 standard inverters:
Line filters
With one of the additional line filters, the Power Module reaches a higher radio interference class.
Line reactors
(only for PM240‑2 Power Modules, frame sizes FSA to FSC, and PM240 FSGX)
Line reactors smooth the current drawn by the inverter and thus reduce harmonic components in the line current. Through the reduction of the current harmonics, the thermal load on the power components in the rectifier and in the DC-b capacitors is reduced as well as the harmonic effects on the supply. The use of a line reactor increases the service life of the inverter.
Note:
A DC b reactor is integrated in the PM240‑2 Power Modules FSD to FSF and therefore no line reactor is required.
Recommended line-side power components
Furthermore, this is a recommendation for additional line-side components, such as fuses and circuit breakers (line-side components must be dimensioned in accordance with IEC standards).
Additional inbation about the line-side power components can be found in Catalogs LV 10, IC 10 and IC 10 AO as well as the Industry Mall.
The following DC b components are available for the SINAMICS G120 standard inverters:
Braking resistors
(for PM240 and PM240‑2 Power Modules only)
Excess energy in the DC b is dissipated in the braking resistor. The braking resistors are designed for use with PM240 and PM240‑2 Power Modules. They are equipped with an integrated braking chopper (electronic switch). There is an optional plug-in Braking Module for frame size FSGX.
Braking Module
(for PM240 Power Modules, frame size FSGX only)
A Braking Module and the matching external braking resistor are required to bring drives with a PM240 Power Module, frame size FSGX, to a controlled standstill in the event of a power failure (e.g. emergency retrb or EMERGENCY STOP Category 1) or to limit the DC b voltage during a short period of generator operation. The Braking Module includes the power electronics and the associated control circuit.
The following load-side power components are available for the SINAMICS G120 standard inverters. This means that during operation with output reactors or sine-wave filters, longer, shielded motor cables are possible and the motor service life can be extended:
Output reactors
(not for PM240-2 Power Modules, frame sizes FSD to FSF, as these have an integrated DC b reactor)
Output reactors reduce the rate of voltage rise (dv/dt) and the height of the current peaks, and enable longer motor cables to be connected.
Sine-wave filter
(not available for PM230 and PM240‑2 Power Modules)
Sine-wave filters limit the rate of voltage rise (dv/dt) and the peak voltages on the motor winding. Similar to an output reactor, they enable the connection of longer motor cables.
Further selected supplementary products are available from Siemens Partners.
Please select “Drive Options” as the technology in the "Solution Partner Finder” :
http://www.siemens.com/automation/partnerfinder
Spare Parts Kit for Control Units
The Spare Parts Kit contains small parts for all variants of the following SINAMICS G120 Control Units:
Shield connection kits for PM240‑2 Power Modules
A shield connection kit is supplied as standard with PM240‑2 Power Modules in frame sizes FSA to FSF. This shield connection kit is also available as a spare part.
Shield plates for PM230 Power Modules
PM230 Power Modules in degree of protection IP20, frame sizes FSA to FSC, are supplied with a shield plate for motor and signal cables. This shield plate is also available as a spare part.
Replacement door for PM240 Power Modules, frame size FSGX
A complete replacement door can be ordered for the PM240 Power Module, frame size FSGX.
Terminal cover kits for frame sizes FSD to FSF
The terminal cover kit includes a replacement cover for the connecting terminals. Terminal cover kits, which are suitable for the Power Modules PM230 in degree of protection IP20, standard version, PM240‑2, and PM250 are available.
Replacement connectors for PM240‑2 Power Modules
A set of connectors for the line feeder cable, braking resistor and motor cable can be ordered corresponding to the frame size of the PM240‑2 Power Module.
Fan units for PM230 and PM240‑2 Power Modules
The fans of PM230 and PM240-2 Power Modules are designed for extra long service life. For special requirements, replacement fans are available that can be exchanged quickly and easily.
Replacement fans for PM240 and PM250 Power Modules
The fans of PM240 and PM250 Power Modules are designed for extra long service life. Replacement fans can be ordered for special applications.
The following electronic configuring aids and engineering tools are available for the SINAMICS G120 standard inverters:
The interactive catalog CA 01 – the offline Industry Mall of Siemens on DVD‑ROM – contains over 100 000 products with approximaby 5 million possible drive system product variants. The Drive Technology Configurator (DT Configurator) has been developed to facilitate selection of the correct motor and/or inverter from the wide spectrum of drives. It is integrated in Catalog CA 01 as an add-on on DVD‑ROM.
In addition, the DT Configurator can be used on the Internet without requiring any installation. The DT Configurator can be found in the Siemens Industry Mall at the following address:
http://www.siemens.com/dt-configurator
The SIZER for Siemens Drives engineering tool makes it easy to engineer the SINAMICS drive family. It provides support when selecting the hardware and firmware components necessary to implement a drive task. SIZER for Siemens Drives is designed to support configuring of the entire drive system.
You can find further inbation on the SIZER for Siemens Drives engineering tool in the chapter Engineering tools.
The SIZER for Siemens Drives engineering tool is available free on the Internet at
http://www.siemens.com/sizer
The STARTER commissioning tool allows menu-bed commissioning, optimization and diagnostics. Apart from the SINAMICS drives, STARTER is also suitable for MICROMASTER 4 devices.
You can find further inbation about the STARTER commissioning tool in the chapter Engineering tools.
Additional inbation about the STARTER commissioning tool is available on the Internet at
http://www.siemens.com/starter
SINAMICS Startdrive is a tool for configuring, commissioning, and diagnosing the SINAMICS family of drives and is integrated into the TIA Portal. SINAMICS Startdrive can be used to implement drive tasks with the SINAMICS G110M, SINAMICS G120, SINAMICS G120C, SINAMICS G120D and SINAMICS G120P inverter series. The commissioning tool has been optimized with regard to user friendliness and consistent use of the TIA Portal benefits of a common working environment for PLC, HMI and drives.
You can find further inbation on the SINAMICS Startdrive commissioning tool in the chapter Engineering tools.
The SINAMICS Startdrive commissioning tool is available free on the Internet at
http://www.siemens.com/startdrive
Drive ES is the engineering system that can be used to integrate the communication, configuration and data management functions of Siemens drive technology into the SIMATIC automation world easily, efficiently and cost-effectively. Two software packages are available for SINAMICS – Drive ES Basic and Drive ES PCS.
You can find further inbation about the Drive ES engineering system in the chapter Engineering tools.
Additional inbation about the Drive ES engineering system is available on the Internet at
http://www.siemens.com/drive-es
Unless explicitly specified otherwise, the following technical specifications are valid for all the following components of the SINAMICS G120 standard inverters.
General technical specifications |
|
---|---|
Mechanical ambient conditions |
|
Long-term storage acc. to EN 60721‑3‑1 |
|
|
Class 1M2 |
|
Class 1M2 |
Transport acc. to EN 60721‑3‑2 |
|
|
Class 2M3 |
|
Class 2M2 |
Operation acc. to EN 60721‑3‑3 |
|
|
Class 3M1 |
|
Test Fc (sinusoidal) according to EN 60068‑2‑6
Deflection: 0.075 mm at 10 ... 57 Hz |
|
Test Ea (semi-sinusoidal) according to EN 60068‑2‑27
Acceleration: 49 m/s2 (5 × g) at 30 ms |
|
|
|
Test Fc according to EN 60068‑2‑6
Deflection: 0.075 mm at 10...58 Hz |
|
Test Ea according to EN 60068‑2‑27 Acceleration: 98 m/s2 (10 × g) at 20 ms |
Ambient conditions |
|
Protection class |
Class I (with protective conductor system) and class III (PELV) |
Touch protection |
For the intended purpose |
Permissible ambient and coolant temperature (air) during operation for line-side power components and Power Modules |
|
|
|
|
-10 ... +40 °C (14 ... 104 °F) without derating |
|
-20 ... +40 °C (-4 ... +104 °F) without derating |
|
0 ... 40 ℃ (32 ... 104 °F) without derating |
|
0 ... 40 °C (32 ... 104 °F) without derating |
|
|
|
-10 ... +50 °C (14 ... 122 °F) without derating |
|
-20 ... +50 °C (-4 ... +122 °F) without derating |
|
0 ... 50 °C (32 ... 122 °F) without derating |
|
0 ... 40 °C (32 ... 104 °F) without derating |
Permissible ambient and coolant temperature (air) during operation for Control Units and supplementary system components |
With CU230P‑2 HVAC and CU230P‑2 DP: -10 ... +60 °C (14 ... 140 °F) With CU230P‑2 PN: -10 ... +55 °C (14 ... 131 °F) With CU240B‑2 and CU240E‑2 (without PN): -10 ... +55 °C (14 ... 131 °F) With CU240E‑2 PN and CU240E‑2 PN‑F:-10 ... +53 °C (14 ... 127.4 °F) With CU250S‑2: -10 ... +50 °C (14 ... 122 °F) With IOP/BOP‑2: 0 ... 50 °C (32 ... 122 °F) Derating of 3 K/1000 m (3281 ft) applies to Control Units as of an installation altitude of 1000 m (3281 ft) above sea level. |
Climatic ambient conditions |
|
|
Class 1K4 |
|
Class 2K4 |
|
Better than class 3K3 with regard to
|
Environmental class/harmful chemical substances |
|
|
Class 1C2 |
|
Class 2C2 |
|
Class 3C2 3) |
Organic/biological influences |
|
|
Class 1B1 |
|
Class 2B1 |
|
Class 3B1 |
Degree of pollution |
2 |
Certification for fail-safe versions |
|
Applies to Control Units of the CU240E‑2 and CU250S‑2 series. The values include Control Unit and Power Module.
Note: |
The PM240‑2 Power Modules, frame sizes FSD to FSF additionally offer STO acc. to IEC 61508 SIL 3 and EN ISO 13489‑1 PL e and Category 3. |
|
SIL 2 |
|
PL d and Category 3 |
Standards |
|
Compliance with standards |
UL 4), cUL 4), CE, C-Tick (RCM), SEMI F47 Additionally for PM240‑2 frame sizes FSD ... FSF: KCC, WEEE, RoHS, EAC |
CE marking |
According to Low-Voltage Directive 2006/95/EC |
EMC Directive acc. to EN 61800‑3 |
|
Interference immunity |
|
PM230 Power Modules, with degree of protection IP20 |
The Power Modules are tested according to the interference immunity requirements for environments according to Category C3 |
Interference emissions |
|
PM230 Power Modules with degree of protection IP20 |
|
|
5) |
|
Observance of the limit values according to Category C3 and C2 6) |
|
Observance of the limit values
|
PM240‑2 Power Modules |
|
|
5) |
|
Observance of the limit values
|
|
Observance of the limit values according to Category C3 and C2 6) |
|
Observance of the limit values
|
PM240 Power Modules |
|
|
5) |
|
Observance of the limit values
|
PM250 Power Modules |
|
|
Observance of the limit values according to Category C3 and C2 6) |
|
Observance of the limit values
|
|
5) |
|
Observance of the limit values according to Category C3 and C2 6) |
1) In product packaging.
2) In transport packaging.
3) SIPLUS components for extreme requirements are available. Additional inbation is available on the Internet athttp://www.siemens.com/siplus-drives
4) Applies to all PM230 Power Modules in degree of protection IP20 (cUL only for frame sizes FSA to FSC), PM240‑2, PM240 and PM250 Power Modules with integrated line filter class A.
5) Non-filtered devices are designed for operation on IT systems or in conjunction with an RCD. The customer must provide suitable RI suppression equipment to ensure that these devices comply with the limits defined for Category C3 or C2.
6) Max. permissible cable lengths see section Power Modules → Integration.
Note:
The EMC product standard EN 61800-3 does not apply directly to a frequency inverter but to a PDS (Power Drive System), which comprises the complete circuitry, motor and cables in addition to the inverter. The frequency inverters on their own do not generally require identification according to the EMC Directive.
CE marking
The SINAMICS G120 inverters meet the requirements of the Low-Voltage Directive 2006/95/EC.
Low-Voltage Directive
The inverters comply with the following standards listed in the official journal of the EU:
UL listing
Inverter devices in UL category NMMS certified to UL and cUL, in compliance with UL508C. UL list numbers E121068 and E192450. This applies to all PM230 Power Modules, IP 20 degree of protection (cUL only for frame sizes FSA to FSC), PM240, PM240‑2 and PM250 Power Modules with integrated line filter class A.
For use in environments with pollution degree 2.
See also on the Internet at
http://www.ul.com
Machinery Directive
The inverters are suitable for installation in machines. Compliance with the Machinery Directive 2006/42/EC requires a separate certificate of conbity. This must be provided by the plant construction company or the organization marketing the machine.
EMC directive
The following inbation applies to SINAMICS G120 frequency inverters from Siemens AG:
SEMI F47
SEMI F47 is an industry standard relating to the immunity to voltage dips. This includes the requirement that industrial equipment must be able to tolerate defined dips or drops of the line supply voltage. As a result, industrial equipment that fulfills this standard is more reliable and productive. In the SINAMICS G120 product family, the PM230, PM240, PM240‑2 and PM250 Power Modules fulfill the latest SEMI F47‑0706 standard. In the case of a voltage dip, defined in accordance with SEMI F47‑0607, these drives either continue to supply a defined output current, or using an automatic restart function, continue to operate as expected.