6ES7307-1EA01-0AA0西門子S7-300 調(diào)節(jié)電源 PS307 6ES7307-1EA01-0AA0西門子S7-300 調(diào)節(jié)電源 PS307
西門子工業(yè)產(chǎn)品銷售熱線:15618032370 QQ:282119341
產(chǎn)品信息:
SIMATIC PS 307 單相負(fù)載電源(系統(tǒng)和負(fù)載電源)帶輸入電壓范圍自動(dòng)選擇功能。其設(shè)計(jì)和功能非常適用于 SIMATIC S7-300 PLC。 借助于隨該系統(tǒng)和負(fù)載電源提供的連接梳形件,可迅速建立與 CPU 電源連接。 它也可以向其它 S7-300 系統(tǒng)部件、輸入/輸出模塊的輸入/輸出電路以及(如有必要)傳感器和執(zhí)行器提供 24 V 電源。 該電源通過(guò)了全面認(rèn)證(如 UL、ATEX 或 GL),可以通用(不適合室外應(yīng)用)。
Article number |
6ES7307-1BA01-0AA0 |
6ES7305-1BA80-0AA0 |
6ES7307-1EA01-0AA0 |
6ES7307-1EA80-0AA0 |
6ES7307-1KA02-0AA0 |
|
---|---|---|---|---|---|---|
Product |
PS 307 |
PS 305 Outdoor |
PS 307 |
PS 307 Outdoor |
PS 307 |
|
Power supply, type |
24 V/2 A |
24 V/2 A |
24 V/5 A |
24 V/5 A |
24 V/10 A |
|
Input |
|
|
|
|
|
|
Input |
1-phase AC |
DC voltage |
1-phase AC |
1-phase AC |
1-phase AC |
|
Supply voltage |
|
|
|
|
|
|
|
120 V |
|
120 V |
120 V |
120 V |
|
|
230 V |
|
230 V |
230 V |
230 V |
|
|
|
24 ... 110 V |
|
|
|
|
|
Automatic range selection |
|
Automatic range selection |
Set by means of selector switch on the device |
Automatic range selection |
|
Input voltage |
|
|
|
|
|
|
|
85 ... 132 V |
|
85 ... 132 V |
93 ... 132 V |
85 ... 132 V |
|
|
170 ... 264 V |
|
170 ... 264 V |
187 ... 264 V |
170 ... 264 V |
|
|
|
16.8 ... 138 V |
|
|
|
|
Wide-range b |
No |
Yes |
No |
No |
No |
|
Overvoltage resistance |
2.3 × Vin rated, 1.3 ms |
154 V; 0.1 s |
2.3 × Vin rated, 1.3 ms |
2.3 × Vin rated, 1.3 ms |
2.3 × Vin rated, 1.3 ms |
|
Mains buffering at Iout rated, min. |
20 ms; at Vin = 93/187 V |
10 ms; at Vin rated |
20 ms; at Vin = 93/187 V |
20 ms; at Vin = 93/187 V |
20 ms; at Vin = 93/187 V |
|
Rated line frequency 1 |
50 Hz |
|
50 Hz |
50 Hz |
50 Hz |
|
Rated line frequency 2 |
60 Hz |
|
60 Hz |
60 Hz |
60 Hz |
|
Rated line range |
47 ... 63 Hz |
|
47 ... 63 Hz |
47 ... 63 Hz |
47 ... 63 Hz |
|
Input current |
|
|
|
|
|
|
|
0.9 A |
|
2.3 A |
2.1 A |
4.2 A |
|
|
0.5 A |
|
1.2 A |
1.2 A |
1.9 A |
|
|
|
2.4 A |
|
|
|
|
|
|
0.6 A |
|
|
|
|
Switch-on current limiting (+25 °C), max. |
22 A |
20 A |
20 A |
45 A |
55 A |
|
Duration of inrush current limiting at 25 °C |
|
|
|
|
|
|
|
3 ms |
10 ms |
3 ms |
3 ms |
3 ms |
|
I2t, max. |
1 A2·s |
5 A2·s |
1.2 A2·s |
1.8 A2·s |
3.3 A2·s |
|
Built-in incoming fuse |
T 1.6 A/250 V (not accessible) |
T 6.3 A/250 V (not accessible) |
T 3,15 A/250 V (not accessible) |
T 3,15 A/250 V (not accessible) |
T 6.3 A/250 V (not accessible) |
|
Protection in the mains power b (IEC 898) |
Recommended miniature circuit breaker: 3 A characteristic C |
Recommended miniature circuit breaker: from 10 A characteristic C, suitable for DC |
Recommended miniature circuit breaker: from 6 A characteristic C |
Recommended miniature circuit breaker: from 10 A characteristic C or from 6 A characteristic D |
Recommended miniature circuit breaker: from 10 A characteristic C |
|
Output |
|
|
|
|
|
|
Output |
Controlled, isolated DC voltage |
Controlled, isolated DC voltage |
Controlled, isolated DC voltage |
Controlled, isolated DC voltage |
Controlled, isolated DC voltage |
|
Rated voltage Vout DC |
24 V |
24 V |
24 V |
24 V |
24 V |
|
Total tolerance, static ± |
3 % |
3 % |
3 % |
3 % |
3 % |
|
Static mains compensation, approx. |
0.1 % |
0.2 % |
0.1 % |
0.2 % |
0.1 % |
|
Static load balancing, approx. |
0.2 % |
0.4 % |
0.5 % |
0.4 % |
0.5 % |
|
Residual ripple peak-peak, max. |
50 mV |
150 mV |
50 mV |
150 mV |
50 mV |
|
Residual ripple peak-peak, typ. |
5 mV |
30 mV |
10 mV |
40 mV |
15 mV |
|
Spikes peak-peak, max. (bandb: 20 MHz) |
150 mV |
240 mV |
150 mV |
240 mV |
150 mV |
|
Spikes peak-peak, typ. (bandb: 20 MHz) |
20 mV |
150 mV |
20 mV |
90 mV |
60 mV |
|
Product function Output voltage adjustable |
No |
No |
No |
No |
No |
|
Output voltage setting |
- |
- |
- |
- |
- |
|
Status display |
Green LED for 24 V OK |
Green LED for 24 V OK |
Green LED for 24 V OK |
Green LED for 24 V OK |
Green LED for 24 V OK |
|
On/off behavior |
No overshoot of Vout (soft start) |
No overshoot of Vout (soft start) |
No overshoot of Vout (soft start) |
No overshoot of Vout (soft start) |
No overshoot of Vout (soft start) |
|
Startup delay, max. |
2 s |
3 s |
2 s |
3 s |
2 s |
|
Voltage rise, typ. |
10 ms |
5 ms |
10 ms |
100 ms |
10 ms |
|
Rated current value Iout rated |
2 A |
2 A |
5 A |
5 A |
10 A |
|
Current range |
0 ... 2 A |
0 ... 3 A |
0 ... 5 A |
0 ... 5 A |
0 ... 10 A |
|
|
|
3 A up to +60°C at Vin > 24 V |
|
|
|
|
Supplied active power typical |
48 W |
48 W |
120 W |
120 W |
240 W |
|
Short-term overload current |
|
|
|
|
|
|
|
9 A |
9 A |
20 A |
20 A |
38 A |
|
|
9 A |
9 A |
20 A |
20 A |
38 A |
|
Duration of overloading capability for excess current |
|
|
|
|
|
|
|
90 ms |
270 ms |
100 ms |
180 ms |
80 ms |
|
|
90 ms |
270 ms |
100 ms |
80 ms |
80 ms |
|
Parallel switching for enhanced perbance |
Yes |
Yes |
Yes |
No |
Yes |
|
Numbers of parallel switchable units for enhanced perbance |
2 |
2 |
|
|
|
|
Efficiency |
|
|
|
|
|
|
Efficiency at Vout rated, Iout rated, approx. |
84 % |
75 % |
87 % |
84 % |
90 % |
|
Power loss at Vout rated, Iout rated, approx. |
9 W |
16 W |
18 W |
23 W |
27 W |
|
Closed-loop control |
|
|
|
|
|
|
Dynamic mains compensation (Vin rated ±15 %), max. |
0.1 % |
0.3 % |
0.1 % |
0.3 % |
0.1 % |
|
Dynamic load smoothing (Iout: 50/100/50 %), Uout ± typ. |
0.8 % |
2.5 % |
1 % |
3 % |
2 % |
|
Load step setting time 50 to 100%, typ. |
0.5 ms |
2.5 ms |
0.3 ms |
0.2 ms |
|
|
Load step setting time 100 to 50%, typ. |
0.5 ms |
2.5 ms |
0.3 ms |
0.2 ms |
|
|
Setting time maximum |
1 ms |
5 ms |
|
5 ms |
0.1 ms |
|
Protection and monitoring |
|
|
|
|
|
|
Output overvoltage protection |
Additional control loop, shutdown at < 28.8 V, automatic restart |
Additional control loop, shutdown at approx. 30 V, automatic restart |
Additional control loop, shutdown at < 28.8 V, automatic restart |
Additional control loop, shutdown at approx. 30 V, automatic restart |
Additional control loop, shutdown at < 28.8 V, automatic restart |
|
Current limitation |
2.2 ... 2.6 A |
3.3 ... 3.9 A |
5.5 ... 6.5 A |
5.5 ... 6.5 A |
11 ... 12 A |
|
Property of the output Short-circuit proof |
Yes |
Yes |
Yes |
Yes |
Yes |
|
Short-circuit protection |
Electronic shutdown, automatic restart |
Electronic shutdown, automatic restart |
Electronic shutdown, automatic restart |
Electronic shutdown, automatic restart |
Electronic shutdown, automatic restart |
|
Enduring short circuit current RMS value |
|
|
|
|
|
|
|
2 A |
2 A |
7 A |
5 A |
12 A |
|
Overload/short-circuit indicator |
- |
- |
|
|
- |
|
Safety |
|
|
|
|
|
|
Primary/secondary isolation |
Yes |
Yes |
Yes |
Yes |
Yes |
|
Galvanic isolation |
Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178 |
Safety extra low output voltage Vout according to EN 60950-1 and EN 50178, creepage distances and bances > 5 mm |
Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178 |
Safety extra low output voltage Vout according to EN 60950-1 and EN 50178, creepage distances and bances > 5 mm |
Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178 |
|
Protection class |
Class I |
Class I |
Class I |
Class I |
Class I |
|
Leakage current |
|
|
|
|
|
|
|
3.5 mA |
|
3.5 mA |
3.5 mA |
3.5 mA |
|
|
0.5 mA |
|
0.5 mA |
0.3 mA |
0.6 mA |
|
CE mark |
Yes |
Yes |
Yes |
Yes |
Yes |
|
UL/cUL (CSA) approval |
cULus-Listed (UL 508, CSA C22.2 No. 142), File E143289 |
UL-Listed (UL 508), File E143289, CSA (CSA C22.2 No. 142) |
cULus-Listed (UL 508, CSA C22.2 No. 142), File E143289 |
UL-Listed (UL 508), File E143289, CSA (CSA C22.2 No. 142) |
cULus-Listed (UL 508, CSA C22.2 No. 142), File E143289 |
|
Explosion protection |
ATEX (EX) II 3G Ex nA II T4; cULus (ISA 12.12.01, CSA C22.2 No.213) Class I, Div. 2, Group ABCD, T4, File E330455 |
- |
ATEX (EX) II 3G Ex nA II T4; cULus (ISA 12.12.01, CSA C22.2 No.213) Class I, Div. 2, Group ABCD, T4, File E330455 |
- |
ATEX (EX) II 3G Ex nA II T4; cULus (ISA 12.12.01, CSA C22.2 No.213) Class I, Div. 2, Group ABCD, T4, File E330455 |
|
FM approval |
Class I, Div. 2, Group ABCD, T4 |
- |
Class I, Div. 2, Group ABCD, T4 |
- |
Class I, Div. 2, Group ABCD, T4 |
|
CB approval |
No |
No |
No |
No |
No |
|
Marine approval |
In S7-300 system |
- |
In S7-300 system |
- |
In S7-300 system |
|
Degree of protection (EN 60529) |
IP20 |
IP20 |
IP20 |
IP20 |
IP20 |
|
EMC |
|
|
|
|
|
|
Emitted interference |
EN 55022 Class B |
EN 55011 Class A |
EN 55022 Class B |
EN 55011 Class A |
EN 55022 Class B |
|
Supply harmonics limitation |
not applicable |
not applicable |
EN 61000-3-2 |
- |
EN 61000-3-2 |
|
Noise immunity |
EN 61000-6-2 |
EN 61000-6-2 |
EN 61000-6-2 |
EN 61000-6-2 |
EN 61000-6-2 |
|
Operating data |
|
|
|
|
|
|
Ambient temperature |
|
|
|
|
|
|
|
0 ... 60 °C |
-25 ... +70 °C |
0 ... 60 °C |
-25 ... +70 °C |
0 ... 60 °C |
|
|
with natural convection |
with natural convection |
with natural convection |
with natural convection |
with natural convection |
|
|
-40 ... +85 °C |
-40 ... +85 °C |
-40 ... +85 °C |
-40 ... +85 °C |
-40 ... +85 °C |
|
|
-40 ... +85 °C |
-40 ... +85 °C |
-40 ... +85 °C |
-40 ... +85 °C |
-40 ... +85 °C |
|
Humidity class according to EN 60721 |
Climate class 3K3, no condensation |
Climate class 3K5, transient condensation permitted |
Climate class 3K3, no condensation |
Climate class 3K5, transient condensation permitted |
Climate class 3K3, no condensation |
|
Mechanics |
|
|
|
|
|
|
Connection technology |
screw-type terminals |
screw-type terminals |
screw-type terminals |
screw-type terminals |
screw-type terminals |
|
Connections |
|
|
|
|
|
|
|
L, N, PE: 1 screw terminal each for 0.5 ... 2.5 mm2 single-core/finely stranded |
L+1, M1, PE: 1 screw terminal each for 0.5 ... 2.5 mm2 single-core/finely stranded |
L, N, PE: 1 screw terminal each for 0.5 ... 2.5 mm2 single-core/finely stranded |
L, N, PE: 1 screw terminal each for 0.5 ... 2.5 mm2 single-core/finely stranded |
L, N, PE: 1 screw terminal each for 0.5 ... 2.5 mm2 single-core/finely stranded |
|
|
L+, M: 2 screw terminals each for 0.5 ... 2.5 mm2 |
L+, M: 3 screw terminals each for 0.5 ... 2.5 mm2 |
L+, M: 3 screw terminals each for 0.5 ... 2.5 mm2 |
L+, M: 3 screw terminals each for 0.5 ... 2.5 mm2 |
L+, M: 4 screw terminals each for 0.5 ... 2.5 mm2 |
|
|
- |
- |
- |
- |
- |
|
Width of the enclosure |
40 mm |
80 mm |
60 mm |
80 mm |
80 mm |
|
Height of the enclosure |
125 mm |
125 mm |
125 mm |
125 mm |
125 mm |
|
Depth of the enclosure |
120 mm |
120 mm |
120 mm |
120 mm |
120 mm |
|
Required spacing |
|
|
|
|
|
|
|
40 mm |
50 mm |
40 mm |
50 mm |
40 mm |
|
|
40 mm |
50 mm |
40 mm |
50 mm |
40 mm |
|
|
0 mm |
0 mm |
0 mm |
0 mm |
0 mm |
|
|
0 mm |
0 mm |
0 mm |
0 mm |
0 mm |
|
Weight, approx. |
0.4 kg |
0.57 kg |
0.6 kg |
0.57 kg |
0.8 kg |
|
Product feature of the enclosure housing for side-by-side mounting |
Yes |
Yes |
Yes |
Yes |
Yes |
|
Installation |
Can be mounted onto S7 rail |
Can be mounted onto S7 rail |
Can be mounted onto S7 rail |
Can be mounted onto S7 rail |
Can be mounted onto S7 rail |
|
Mechanical accessories |
Mounting adapter for standard mounting rail (6EP1971-1BA00) |
Mounting adapter for standard mounting rail (6ES7390-6BA00-0AA0) |
Mounting adapter for standard mounting rail (6EP1971-1BA00) |
Mounting adapter for standard mounting rail (6ES7390-6BA00-0AA0) |
Mounting adapter for standard mounting rail (6EP1971-1BA00) |
|
MTBF at 40 °C |
2 320 078 h |
964 506 h |
2 480 589 h |
2 231 610 h |
1 504 280 h |
|
Other inbation |
Specifications at rated b voltage and ambient temperature +25 °C (unless otherwise specified) |
Specifications at rated b voltage and ambient temperature +25 °C (unless otherwise specified) |
Specifications at rated b voltage and ambient temperature +25 °C (unless otherwise specified) |
Specifications at rated b voltage and ambient temperature +25 °C (unless otherwise specified) |
Specifications at rated b voltage and ambient temperature +25 °C (unless otherwise specified |